Commission Decision of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof (notified under document number C(2000) 1001) (Text with EEA relevance) (2000/367/EC)
Consolidated text: Commission Decision of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof (notified under document number C(2000) 1001) (Text with EEA relevance) (2000/367/EC)
Commission Decision of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof (notified under document number C(2000) 1001) (Text with EEA relevance) (2000/367/EC)
No longer in force
02000D0367 — EN — 12.04.2011 — 002.001
This text is meant purely as a documentation tool and has no legal effect. The Union's institutions do not assume any liability for its contents. The authentic versions of the relevant acts, including their preambles, are those published in the Official Journal of the European Union and available in EUR-Lex. Those official texts are directly accessible through the links embedded in this document
|
COMMISSION DECISION of 3 May 2000 implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof (notified under document number C(2000) 1001) (Text with EEA relevance) (OJ L 133 6.6.2000, p. 26) |
Amended by:
|
|
|
Official Journal |
||
|
No |
page |
date |
||
|
L 218 |
51 |
30.8.2003 |
||
|
L 97 |
49 |
12.4.2011 |
||
Corrected by:
COMMISSION DECISION
of 3 May 2000
implementing Council Directive 89/106/EEC as regards the classification of the resistance to fire performance of construction products, construction works and parts thereof
(notified under document number C(2000) 1001)
(Text with EEA relevance)
(2000/367/EC)
Article 1
The classification system adopted at Community level for the resistance to fire performance of construction products, construction works and parts thereof shall be as set out in the Annex.
Article 2
This Decision is addressed to the Member States.
ANNEX
DEFINITIONS, TESTS AND PERFORMANCE CRITERIA
The relevant definitions, tests and performance criteria are fully described in, or referenced from, the European standards referred to in this Annex.
SYMBOLS
|
R |
Load-bearing capacity |
|
E |
Integrity |
|
I |
Insulation |
|
W |
Radiation |
|
M |
Mechanical action |
|
C |
Self-closing |
|
S |
Smoke leakage |
|
P or PH |
Continuity of power and/or signal supply |
|
G |
Soot fire resistance |
|
K |
Fire protection ability |
|
D |
Stability duration under constant temperature |
|
DH |
Stability duration under the standard time-temperature curve |
|
F |
Functionality of powered smoke and heat ventilators |
|
B |
Functionality of natural smoke and heat ventilators |
Notes
1. The following classifications are expressed in minutes unless otherwise specified.
2. The European standards EN 13501-2, EN 13501-3 ►M1 , EN 13501-4 ◄ (classification) and EN 1992-1.2, EN 1993-1.2, EN 1994-1.2, EN 1995-1.2, EN 1996-1.2, EN 1999-1.2 (Eurocodes) referred to in this Decision shall be subject to the same safeguard procedures as described in Article 5(1) of Directive 89/106/EEC.
CLASSIFICATIONS
1. Load-bearing elements without a fire separating function
|
Applies to |
walls, floors, roofs, beams, columns, balconies, stairs, walkways |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1365-1,2,3,4,5,6; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2 |
|||||||||
|
Classification: |
||||||||||
|
R |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
360 |
|
Notes |
— |
|||||||||
2. Load-bearing elements with a fire-separating function
|
Applies to |
Walls |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1365-1; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2 |
|||||||||
|
Classification: |
||||||||||
|
RE |
|
20 |
30 |
|
60 |
90 |
120 |
180 |
240 |
►M1 360 ◄ |
|
REI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
►M1 360 ◄ |
|
REI-M |
|
|
30 |
|
60 |
90 |
120 |
180 |
240 |
►M1 360 ◄ |
|
REW |
|
20 |
30 |
|
60 |
90 |
120 |
180 |
240 |
►M1 360 ◄ |
|
Notes |
— |
|||||||||
|
Applies to |
floors and roofs |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1365-2; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1999-1.2 |
|||||||||
|
Classification: |
||||||||||
|
R |
|
|
30 |
|
|
|
|
|
|
|
|
RE |
|
20 |
30 |
|
60 |
90 |
120 |
180 |
240 |
►M1 360 ◄ |
|
REI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
►M1 360 ◄ |
|
Notes |
— |
|||||||||
3. Products and systems for protecting load-bearing elements or parts of the works
|
Applies to |
ceilings with no independent fire resistance |
|
Standard(s) |
EN 13501-2; prEN 13381-1 |
|
Classification: expressed in the same terms as the load-bearing element being protected |
|
|
Notes |
If also fulfilling the requirement with regard to the ‘semi-natural’ fire, the symbol ‘sn’ is added to the classification. |
|
Applies to |
fire protective coatings, boards, renderings, claddings and screens |
|
Standard(s) |
EN 13501-2; prEN 13381-2 to 8 |
|
Classification: expressed in the same terms as the load-bearing element being protected |
|
|
Notes |
— |
4. Non-loadbearing elements or parts of works and products therefor
|
Applies to |
partitions (including partitions incorporating uninsulated portions, and cavity barriers) |
|||||||||
|
Standard(s) |
EN13501-2; EN 1364-1 (1); EN 1992-1-2; EN 1993-1-2; EN 1994-1-2; EN 1995-1-2; EN 1996-1-2; EN 1999-1-2 |
|||||||||
|
Classification: - |
|
|||||||||
|
E |
|
20 |
30 |
|
60 |
90 |
120 |
|
|
|
|
EI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
EI-M |
|
|
30 |
|
60 |
90 |
120 |
180 |
240 |
|
|
EW |
|
20 |
30 |
|
60 |
90 |
120 |
|
|
|
|
Notes |
— |
|||||||||
|
(1)
For cavity barriers this standard is complemented by EOTA TR 031. |
||||||||||
|
Applies to |
ceilings with independent fire resistance |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1364-2 |
|||||||||
|
Classification: |
||||||||||
|
EI |
15 |
|
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
Notes |
The classification is completed by ‘(a → b)’, ‘(b → a)’, or ‘(a ↔ b)’ to indicate whether the element has been tested and fulfils the requirements from above or below only or both. |
|||||||||
|
Applies to |
facades (curtain walls) and external walls (including glazed elements) |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1364-3,4,5,6; EN 1992-1.2; EN 1993-1.2; EN 1994-1.2; EN 1995-1.2; EN 1996-1.2; EN 1999-1.2 |
|||||||||
|
Classification: |
||||||||||
|
E |
15 |
|
30 |
|
60 |
90 |
120 |
|
|
|
|
EI |
15 |
|
30 |
|
60 |
90 |
120 |
|
|
|
|
EW |
|
20 |
30 |
|
60 |
|
|
|
|
|
|
Notes |
The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. Where required, mechanical stability means that there are no falling parts liable to cause personal injury during the time for the E or EI classification. |
|||||||||
|
Applies to |
raised floors |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1366-6 |
|||||||||
|
Classification: |
||||||||||
|
R |
15 |
|
30 |
|
|
|
|
|
|
|
|
RE |
|
|
30 |
|
|
|
|
|
|
|
|
REI |
|
|
30 |
|
|
|
|
|
|
|
|
Notes |
The classification is completed by the addition of the suffix ‘f’ to indicate full fire resistance or ‘r’ to indicate exposure to the reduced constant temperature exposure only. |
|||||||||
|
Applies to |
penetration seals and linear gap seals |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1366-3,4 |
|||||||||
|
Classification: |
||||||||||
|
E |
15 |
|
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
EI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
Notes |
— |
|||||||||
|
Applies to |
fire doors and shutters (including those that incorporate glazing and hardware) and their closing devices |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1634-1 |
|||||||||
|
Classification: |
||||||||||
|
E |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
EI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
EW |
|
20 |
30 |
|
60 |
|
|
|
|
|
|
Notes |
The I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) (1). |
|||||||||
|
(1)
The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification. |
||||||||||
|
Applies to |
smoke control doors |
|
Standard(s) |
EN 13501-2; EN 1634-3 |
|
Classification: S200 or Sa depending upon the test conditions fulfilled |
|
|
Notes |
The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) (1). |
|
(1)
The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification. |
|
|
Applies to |
closures for conveyers and trackbound transportation systems |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1366-7 |
|||||||||
|
Classification: |
||||||||||
|
E |
15 |
|
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
EI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
EW |
|
20 |
30 |
|
60 |
|
|
|
|
|
|
Notes |
►M1 The I classification is completed by the addition of the suffix ‘1’ or ‘2’ to indicate which definition of insulation is used. An I classification shall be generated for those cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system. The addition of the symbol ‘C’ indicates that the product also satisfies the ‘self-closing’ criterion (pass/fail test) (1) ◄ . |
|||||||||
|
(1)
The ‘C’ classification may be complemented by the digits 0 to 5 according to the use category. Details shall be included in the relevant product technical specification. |
||||||||||
|
Applies to |
service ducts and shafts |
|||||||||
|
Standard(s) |
EN 13501-2; EN 1366-5 |
|||||||||
|
Classification: |
||||||||||
|
E |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
EI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
Notes |
The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. |
|||||||||
|
Applies to |
chimneys |
|
Standard(s) |
EN 13501-2; EN 13216 |
|
Classification: G + distance in mm (e.g. G 50) |
|
|
Notes |
Distance not required for built-in products. |
|
Applies to |
Wall and ceiling coverings |
||||||||
|
Standard(s) |
EN 13501-2; EN 14135 |
||||||||
|
Classification: |
|||||||||
|
K1 |
10 |
|
|
|
|
|
|
|
|
|
K2 |
10 |
|
30 |
|
60 |
|
|
|
|
|
Notes The suffixes ‘1’ and ‘2’ indicate which substrates, fire behaviour criteria and extension rules are used in this classification. |
|||||||||
5. Products for use in ventilation systems (excluding smoke and heat exhaust ventilation)
|
Applies to |
ventilation ducts |
|||||||||
|
Standard(s) |
EN 13501-3; EN 1366-1 |
|||||||||
|
Classification: |
||||||||||
|
EI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
E |
|
|
30 |
|
60 |
|
|
|
|
|
|
Notes |
The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. The addition of the symbol ‘S’ indicates the satisfaction of an extra restriction on leakage. |
|||||||||
|
Applies to |
fire dampers |
|||||||||
|
Standard(s) |
EN 13501-3; EN 1366-2 |
|||||||||
|
Classification: |
||||||||||
|
EI |
15 |
20 |
30 |
45 |
60 |
90 |
120 |
180 |
240 |
|
|
E |
|
|
30 |
|
60 |
90 |
120 |
|
|
|
|
Notes |
The classification is completed by ‘(i → o)’, ‘(o → i)’, or ‘(i ↔ o)’ to indicate whether the element has been tested and fulfils the requirements from the inside or outside only or both. In addition, the symbolts ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. The addition of the symbol ‘S’ indicates the satisfaction of an extra restriction on leakage. |
|||||||||
6. Products to be used within services
|
Applies to |
electrical and fibre-optic cables and accessories; conduits and fire protective systems for cables |
|||||||||
|
Standard(s) |
EN 13501-3 |
|||||||||
|
Classification: |
||||||||||
|
P |
15 |
|
30 |
|
60 |
90 |
120 |
|
|
|
|
Notes |
— |
|||||||||
|
Applies to |
small diameter power or signal cables or systems (<20 mm diameter and with conductor sizes ≤2.5 mm2) |
|||||||||
|
Standard(s) |
EN 13501-3; EN 50200 |
|||||||||
|
Classification: |
||||||||||
|
PH |
15 |
|
30 |
|
60 |
90 |
120 |
|
|
|
|
Notes |
— |
|||||||||
7. Products to be used in smoke and heat control systems
The standards cited in this section are under preparation and may be due to revision or upgrade.
|
Applies to |
Single compartment smoke control ducts |
|||||||||
|
Standard(s) |
EN 13501-4; EN 1363-1, 2, 3; EN 1366-9 EN 12101-7 |
|||||||||
|
Classification: — |
||||||||||
|
E300 |
|
|
30 |
|
60 |
90 |
120 |
|
|
|
|
E600 |
|
|
30 |
|
60 |
90 |
120 |
|
|
|
|
Notes The classification is completed by the suffix ‘single’ to indicate suitability for single compartment use only. In addition, the symbols, ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. ‘S’ indicates a leakage rate of less than 5 m3/hr/m2 (All ducts without an ‘S’ classification must have a leakage rate of less than 10 m3/hr/m2) ‘500’, ‘1 000 ’, ‘1 500 ’ indicate the suitability for use up to these values of pressure, measured at ambient. |
||||||||||
|
Applies to |
Multi-compartment fire resistant smoke control ducts |
|||||||||
|
Standard(s) |
EN 13501-4; EN 1363-1, 2, 3; EN 1366-8; EN 12101-7 |
|||||||||
|
Classification: — |
||||||||||
|
EI |
|
|
30 |
|
60 |
90 |
120 |
|
|
|
|
Notes The classification is completed by the suffix ‘multi’ to indicate suitability for multi-compartment use. In addition, the symbols ‘ve’ and/or ‘ho’ indicate the suitability for vertical and/or horizontal use. ‘S’ indicates a leakage rate of less than 5 m3/hr/m2 (All ducts without an ‘S’ classification must have a leakage rate of less than 10 m3/hr/m2) ‘500’, ‘1 000 ’, ‘1 500 ’ indicate the suitability for use up to these values of pressure, measured at ambient. |
||||||||||
|
Applies to |
Single compartment smoke control dampers |
|||||||||
|
Standard(s) |
EN 13501-4; EN 1363-1, 3; EN 1366- 9, 10; EN 12101-8 |
|||||||||
|
Classification: — |
||||||||||
|
E300 |
|
|
30 |
|
60 |
90 |
120 |
|
|
|
|
E600 |
|
|
30 |
|
60 |
90 |
120 |
|
|
|
|
Notes The classification is completed by the suffix ‘single’ to indicate suitability for single compartment use. ‘HOT 400/30’ (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C (to be used only with E600 classification). ‘ved’, ‘vew’‘vedw’ and/or ‘hod’, ‘how’‘hodw’ indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively. ‘S’ indicates a leakage rate of less than 200 m3/hr/m2. All dampers without an ‘S’ classification must have a leakage rate of less than 360 m3/hr/m2. All damper less than 200 m3/hr/m2 take this value, all dampers between 200 m3/hr/m2 and 360 m3/hr/m2 take the 360 m3/hr/m2 value. Leakage rates are both at ambient and elevated temperatures. ‘500’, ‘1 000 ’, ‘1 500 ’ indicates the suitability for use up to at these values of under pressure, measured at ambient. ‘AA’ or ‘MA’ indicates automatic activation or manual intervention ‘i→o’, ‘i ←o’, ‘i ↔o’, indicates the performance criteria are satisfied from inside to outside, outside to inside or both respectively. ‘C300’, ‘C10000’, ‘Cmod’ indicates the suitability of the damper for use in smoke control only systems combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems respectively. |
||||||||||
|
Applies to |
Multi-compartment fire resistant smoke control dampers |
|||||||||
|
Standard(s) |
EN 13501-4; EN 1363-1, 2, 3; EN 1366-2, 8, 10; EN 12101-8 |
|||||||||
|
Classification: |
||||||||||
|
EI |
|
|
30 |
|
60 |
90 |
120 |
|
|
|
|
E |
|
|
30 |
|
60 |
90 |
120 |
|
|
|
|
Notes The classification is completed by the suffix ‘multi’ to indicate suitability for multi-compartment use. ‘HOT 400/30’ (high operational temperature) indicates that the damper has the ability to be opened or closed during a period of 30 minutes under temperature conditions below 400 °C. ‘ved’, ‘vew’‘vedw’ and/or ‘hod’, ‘how’‘hodw’ indicate the suitability for vertical and/or horizontal use, together with mounting in a duct or in a wall or both respectively. ‘S’ indicates a leakage rate of less than 200 m3/hr/m2. All dampers without an ‘S’ classification must have a leakage rate of less than 360 m3/hr/m2. All damper less than 200 m3/hr/m2 take this value, all dampers between 200 m3/hr/m2 and 360 m3/hr/m2 take the 360 m3/hr/m2 value. Leakage rates are both at ambient and elevated temperatures. ‘500’, ‘1 000 ’, ‘1 500 ’ indicates the suitability for use up to these values of pressure, measured at ambient. ‘AA’ or ‘MA’ indicates automatic activation or manual intervention ‘i→o’, ‘i ←o’, ‘i ↔o’, indicates that the performance criteria are satisfied from inside to outside, outside to inside or both, respectively. ‘C300’, ‘C10000’, ‘Cmod’ indicates the suitability of the damper for use in smoke control only systems, combined smoke control and environmental systems, or modulating dampers used in combined smoke control and environmental systems, respectively. |
||||||||||
|
Applies to |
Smoke barriers |
|||||||||
|
Standard(s) |
EN 13501-4; EN 1363-1, 2; EN 12101-1 |
|||||||||
|
Classification: D |
||||||||||
|
D600 |
|
|
30 |
|
60 |
90 |
120 |
|
|
A |
|
DH |
|
|
30 |
|
60 |
90 |
120 |
|
|
A |
|
Notes ‘A’ can be any time over 120 minutes. |
||||||||||
|
Applies to |
Powered smoke and heat exhaust ventilators (fans), connecting joints |
|||||||||
|
Standard(s) |
EN13501-4; EN 1363-1; EN 12101-3; ISO 834-1 |
|||||||||
|
Classification: F |
||||||||||
|
F200 |
|
|
|
|
|
|
120 |
|
|
|
|
F300 |
|
|
|
|
60 |
|
|
|
|
|
|
F400 |
|
|
|
|
|
90 |
120 |
|
|
|
|
F600 |
|
|
|
|
60 |
|
|
|
|
|
|
F842 |
|
|
30 |
|
|
|
|
|
|
|
|
Notes |
||||||||||
|
Applies to |
Natural smoke and heat exhaust ventilators |
|||||||||
|
Standard(s) |
EN 13501-4; EN 1363-1; EN 12101-2 |
|||||||||
|
Classification: B |
||||||||||
|
B300 |
|
|
30 |
|
|
|
|
|
|
|
|
B600 |
|
|
30 |
|
|
|
|
|
|
|
|
Bθ |
|
|
30 |
|
|
|
|
|
|
|
|
Notes Where θ indicates the exposure condition (temperature). |
||||||||||
( 1 ) OJ L 40, 11.2.1989, p. 12.
( 2 ) OJ L 220, 30.8.1993, p. 1.
( 3 ) OJ C 62, 28.2.1994, p. 1.