Commission Delegated Regulation (EU) 2026/557 of 16 March 2026 supplementing Regulation (EU) 2024/3110 of the European Parliament and of the Council by determining classes of performance in relation to the essential characteristic resistance to fire

C/2026/1640

OJ L, 2026/557, 3.6.2026, ELI: http://data.europa.eu/eli/reg_del/2026/557/oj (BG, ES, CS, DA, DE, ET, EL, EN, FR, GA, HR, IT, LV, LT, HU, MT, NL, PL, PT, RO, SK, SL, FI, SV)

Legal status of the document Date of entry into force unknown (pending notification) or not yet in force., Date of effect: 23/06/2026

ELI: http://data.europa.eu/eli/reg_del/2026/557/oj

European flag

Official Journal
of the European Union

EN

L series


2026/557

3.6.2026

COMMISSION DELEGATED REGULATION (EU) 2026/557

of 16 March 2026

supplementing Regulation (EU) 2024/3110 of the European Parliament and of the Council by determining classes of performance in relation to the essential characteristic resistance to fire

(Text with EEA relevance)

THE EUROPEAN COMMISSION,

Having regard to the Treaty on the Functioning of the European Union,

Having regard to Regulation (EU) 2024/3110 of the European Parliament and of the Council of 27 November 2024 laying down harmonised rules for the marketing of construction products and repealing Regulation (EU) No 305/2011 (1), and in particular Article 5(5), third subparagraph thereof,

Whereas:

(1)

In order to enable manufacturers to declare sufficiently detailed classes of performance of products within the harmonised zone established pursuant to Article 11 of Regulation (EU) 2024/3110, it is necessary to establish classes of performance that are aligned to the latest technological and market developments.

(2)

Classes of performance as regards the essential characteristic resistance to fire were established by Commission Delegated Regulation (EU) 2024/1681 (2) on the basis of Regulation (EU) No 305/2011 of the European Parliament and of the Council (3). However, those classes of performance are not applicable under Regulation (EU) 2024/3110. Therefore, in order to keep the continuity of the system, the CPR Acquis Expert Group advised the Commission to establish the same classes of performance set out by Delegated Regulation (EU) 2024/1681.

(3)

The Commission should therefore determine the classes of performance to be used for the declaration of the essential characteristic resistance to fire,

HAS ADOPTED THIS REGULATION:

Article 1

The classes of performance in relation to the essential characteristic resistance to fire of products shall be those set out in the Annex.

Article 2

This Regulation shall enter into force on the twentieth day following that of its publication in the Official Journal of the European Union.

This Regulation shall be binding in its entirety and directly applicable in all Member States.

Done at Brussels, 16 March 2026.

For the Commission

The President

Ursula VON DER LEYEN


(1)   OJ L, 2024/3110, 18.12.2024, ELI: http://data.europa.eu/eli/reg/2024/3110/oj.

(2)  Commission Delegated Regulation (EU) 2024/1681 of 6 March 2024 supplementing Regulation (EU) No 305/2011 of the European Parliament and of the Council by establishing classes of performance in relation to the resistance to fire of construction products (OJ L, 2024/1681, 13.6.2024, ELI: http://data.europa.eu/eli/reg_del/2024/1681/oj).

(3)  Regulation (EU) No 305/2011 of the European Parliament and of the Council of 9 March 2011 laying down harmonised conditions for the marketing of construction products and repealing Council Directive 89/106/EEC (OJ L 88, 4.4.2011, p. 5, ELI: http://data.europa.eu/eli/reg/2011/305/oj).


ANNEX

A.   SYMBOLS

For the purposes of this Annex, the following symbols apply:

R

Load-bearing capacity

E

Integrity

I

Insulation

W

Radiation

M

Mechanical action

C

Self-closing

C0-5

Durability of self-closing:

Use category (C)

Number of cycles

5

≥ 200 000

4

≥ 100 000

3

≥ 50 000

2

≥ 10 000

1

≥ 500

0

≥ 1

S

Smoke leakage (in context of ventilation systems)/Smoke control (in context of doors)

P

Continuity of power and signal supply under the standard time temperature curve

PH

Continuity of power and signal supply under constant temperature

G/O

Soot fire resistance

K

Fire protection ability

T

Temperature class expressed in maximum gas temperature in °C (operating temperature)

D

Stability duration under constant temperature

DH

Stability duration under the standard time-temperature curve

F

Functionality of powered smoke and heat ventilators

B

Functionality of natural smoke and heat ventilators

B.   CLASSES OF PERFORMANCE IN RELATION TO THE ESSENTIAL CHARACTERISTIC RESISTANCE TO FIRE OF PRODUCTS

General

The relevant definitions, tests and performance criteria are fully described or referenced in the relevant harmonised technical specifications, European assessment documents, and European resistance to fire classification and testing standards.

If for asymmetrical elements the declared class of the element is only valid from one side, this information is provided.

The following classes of performance are expressed in minutes unless otherwise specified:

1.   Load-bearing elements without a fire-separating function

Table 1

Applies to

Walls, floors, raised floors, roofs, beams, columns, balconies, walkways and stairs

R

 

15

20

30

45

60

90

120

180

240

360

2.   Load-bearing elements with a fire-separating function

Table 2.1

Applies to

Walls

RE

 

15

20

30

45

60

90

120

180

240

360

REI

 

15

20

30

45

60

90

120

180

240

360

REI-M

 

15

20

30

45

60

90

120

180

240

360

REW

 

15

20

30

45

60

90

120

180

240

360


Table 2.2

Applies to

Floors, roofs, roof windows, rooflights and shutters

RE

 

15

20

30

45

60

90

120

180

240

360

REI

 

15

20

30

45

60

90

120

180

240

360

C

The C classification may be declared where a self-closing device is fitted, and the element or product was not manually closed for the purpose of the test.

Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out.


Table 2.3

Applies to

Raised floors

RE

 

15

20

30

45

60

90

120

180

240

360

REI

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification is made specific depending on the exposure. The absence of the designation letter ‘r’ refers to standard temperature/time curve exposure (full fire resistance) whereas its presence refers to the constant temperature attack of 500  °C (reduced exposure).

Raised floors satisfying the standard temperature/time curve exposure for a given time are considered to satisfy the reduced exposure conditions for at least the same period.

3.   Products and systems for protecting load-bearing elements

Table 3.1

Applies to

Ceilings with no independent fire resistance

Assessment of the contribution to the fire resistance of structural members: Expressed in terms of classification of the load-bearing element being protected.

Notes

Where the criteria with regard to the ‘semi-natural’ fire are satisfied, the symbol ‘sn’ is added to the classification.


Table 3.2

Applies to

Fire protective coatings (reactive), boards (slabs and mats), renderings (sprays), claddings and screens

Assessment of the contribution to the fire resistance of structural members: Expressed in terms of classification of the load-bearing element being protected.

Notes

For coatings, if satisfying the criteria with regard to the ‘slow heating’ curve, the symbol ‘IncSlow’ is added to the classification.

4.   Non-loadbearing elements or products with a fire-separating function

Table 4.1

Applies to

Partitions (including partitions incorporating uninsulated portions) and fixed windows

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

EI-M

 

15

20

30

45

60

90

120

180

240

360

EW

 

15

20

30

45

60

90

120

180

240

360


Table 4.2

Applies to

Unloaded roofs

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

EW

 

15

20

30

45

60

90

120

180

240

360


Table 4.3

Applies to

Cavity barriers

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification is completed by a separate indication, if the product satisfies the sudden exposure test for cavity barriers.


Table 4.4

Applies to

Ceilings with independent fire resistance

EI

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification is completed by indicating how the element has been tested, and refers to a fire from above ‘(a→b)’ or from below ‘(b→a)’ or both ‘(a↔b)’.


Table 4.5

Applies to

Facades (curtain walls) and external walls (including glazed elements)

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

EW

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification is completed by ‘(i→o)’; ‘(o→i)’; or ‘(i↔o)’ to indicate whether the element has been tested and fulfils the requirements from the inside only; from the outside only; or from both sides respectively.

The addition of the suffix ‘ef’ indicates that the test was performed on the basis of the external fire curve.


Table 4.6

Applies to

Non-mechanical fire barriers for ventilation ductwork

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

Notes

In addition to meeting the requirements related to integrity (E), the non-mechanical fire barrier must also:

(a)

be tested from both sides; and

(b)

achieve 360  m3 /(m2 h) maximum leakage rate with reference to nominal duct cross-sectional area during the fire test.

There is no S classification for this product, as it has no ambient temperature smoke performance.

‘ve’ and/or ‘ho’ indicate that the product is intended to be used for vertical and/or horizontal use.


Table 4.7

Applies to

Penetration seals

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification is expressed in terms of classification of the supporting construction with fire-separating function being penetrated.

The classification of pipe penetration seals is completed by the addition of ‘U/U’, ‘C/U’, ‘U/C’, or ‘C/C’ depending on the tested pipe end configuration inside the furnace and outside the furnace respectively (U – uncapped; C – capped).


Table 4.8

Applies to

Combined penetration seals

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification is expressed in terms of classification of the supporting construction with fire-separating function being penetrated.

The classification is completed with the additional relevant classifications of combined elements as set out in this Annex.


Table 4.9

Applies to

Linear joint seals

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification is completed by the addition of the symbols:

‘H’, or ‘V’, or ‘T’ indicating that the classification is valid for the corresponding orientation (Horizontal supporting construction; Vertical supporting construction – vertical joint; Vertical supporting construction – horizontal joint respectively);

‘M’, or ‘F’, or ‘B’ indicating the type of splices (Manufactured; Field; or Both manufactured and field respectively);

‘X’, or ‘Mxxx’ indicating the movement capability (No movement; or Movement induced (in %) respectively), including the subscript ‘lat’ or ‘shear’ indicating the induced movement;

‘W w1 to w2 ’ indicating the joint width range (in mm) for which the classification criterion is satisfied (w1 being the lower width and w2 the higher width limit).


Table 4.10

Applies to

Fire resisting doorsets, openable windows (in walls and roofs), openable rooflights and shutters (including those that incorporate glazing, closing devices and other building hardware)

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

EW

 

15

20

30

45

60

90

120

180

240

360

S200

For elements and products having passed smoke control criteria depending on test conditions fulfilled.

Sa3 or Sa4

For elements and products having passed smoke control criteria depending on test conditions fulfilled.

C

The C classification may be declared where a self-closing device is fitted and the element or product was not manually closed for the purpose of the test.

Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out.

Notes

The EI classification is completed by the addition of the suffix ‘1 ’ or ‘2 ’ to indicate which definition of insulation is used.

In the case where the classification does not cover heating on both the closing and the opening face, it must be indicated explicitly in the classification.

This table does not include or address products for smoke ventilation.

Additional smoke control classification of large industrial doorsets is possible to a leakage limit of 50  m3 /h.


Table 4.11

Applies to

Closures for conveyers and track bound transportation systems

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

EW

 

15

20

30

45

60

90

120

180

240

360

C

The C classification may be declared where a self-closing device is fitted and the element or product was not manually closed for the purpose of the test.

Optionally, for durability of self-closing, the C classification may be complemented by the digits 0 to 5 according to the use category where cycle testing has been carried out.

Notes

The EI classification is completed by the addition of the suffix ‘1 ’ or ‘2 ’ to indicate which definition of insulation is used. An EI classification must be generated in cases where the test specimen is a pipe or duct configuration with no assessment of the closure for the conveyor system.

Sustained operational capability of any clearing device and/or any separating device for a conveyor system is identified by using a ‘T’.


Table 4.12

Applies to

Air transfer grilles

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

EW

 

15

20

30

45

60

90

120

180

240

360

Notes

If satisfying the criteria with regard to integrity during the open state, the symbol ‘resist flame’ is added to the classification.

If satisfying the criteria with regard to the ‘smouldering’ curve, the symbol ‘IncSlow’ is added to the classification.


Table 4.13

Applies to

Service ducts and shafts

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification indicates how the element has been tested and refers to a fire from the inside ‘(i→o)’ or from the outside ‘(o→i)’ or both ‘(i↔o)’. In addition, the symbols ‘ve’ and/or ‘ho’ indicate that the product is intended to be used for vertical and/or horizontal use.


Table 4.14

Applies to

Chimneys

 

G + distance in mm (e.g. G 50 ) or O + distance in mm (e.g. O 50 )

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

 

T (operating temperature) in °C

80

100

120

140

160

200

250

300

400

450

600

Notes

Distance not required for built-in products.

The classification indicates how the element has been tested and refers to a fire from the outside ‘(o→i)’ or both ‘(i↔o)’.

‘ve’ and/or ‘ho’ indicate that the product is intended to be used for vertical and/or horizontal use.


Table 4.15

Applies to

Wall and ceiling coverings

K1

10

15

20

30

45

60

90

120

180

240

360

K2

10

15

20

30

45

60

90

120

180

240

360

Notes

The suffixes ‘1 ’ and ‘2 ’ indicate which substrates, fire behaviour criteria and extension rules are used in this classification.

5.   Products for use in ventilation systems (excluding smoke and heat exhaust ventilation)

Table 5.1

Applies to

Fire resisting ventilation ducts

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

S

10  m3 /(m2 h) maximum leakage rate with reference to the duct surface area during the fire test.

Notes

In addition to meeting the requirements related to integrity (E) the duct must also achieve 15  m3 /(m2 h) maximum leakage rate with reference to duct surface area during the fire test.

The classification indicates how the element has been tested and refers to a fire from the inside ‘(i→o)’ or from the outside ‘(o→i)’ or both ‘(i↔o)’.

‘ve’ and/or ‘ho’ indicate that the product is intended to be used for vertical and/or horizontal use.

The classification must indicate the pressure difference used in the test.


Table 5.2

Applies to

Fire dampers

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

S

200  m3 /(m2 h) maximum leakage rate with reference to nominal duct cross sectional area:

(a)

smallest size at ambient temperature;

(b)

largest size at ambient temperature and during the fire test.

Notes

In addition to meeting the requirements related to integrity (E) the fire damper must also:

(a)

be tested from both sides; and

(b)

achieve 360  m3 /(m2 h) maximum leakage rate with reference to nominal duct cross sectional area during the fire test.

‘ve’ and/or ‘ho’ indicate that the product is intended to be used for vertical (for example, wall mounted) and/or horizontal (for example, floor mounted) use.

‘H’ indicates a fire damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a horizontal blade axis or geometry.

‘V’ indicates a fire damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a vertical blade axis or geometry.

6.   Products to be used within electrical, power control and communication building service installations

Table 6.1

Applies to

Fire protective systems for cable systems and associated components

P

 

15

20

30

45

60

90

120

180

240

360

Notes

The classification must indicate:

The type of cables which can be installed within the fire protective systems, that is to say any standard cable or only specific cables; and the cables configurations which can be protected and the operating voltage as follows:

either to all types of power cables (rated voltage 300 /500  V) for an operating voltage up to 230 /400  V (three-phase AC);

either to all types of power cables (rated voltage 450 /750  V up to 0,6 /1  kV) for an operating voltage up to 400 /690  V (Three-phase AC);

either to all types of signal-/control cables (rated voltage up to 170  V) for an operating voltage up to 110  V; or

any combination of the above possibilities.


Table 6.2

Applies to

Unprotected electric, power control and communication cables with intrinsic fire resistance

Pca

 

15

20

30

45

60

90

120

180

240

360

Notes

For power cables and control cables, the classification must indicate for which rated voltage the performance criteria are satisfied.


Table 6.3

Applies to

Unprotected small electric, power control and communication cables with intrinsic fire resistance (< 20 mm diameter and with conductor sizes ≤ 2,5 mm2)

PHca

 

15

20

30

45

60

90

120

180

240

360

Notes

For power cables and control cables, the classification must indicate for which rated voltage the performance criteria are satisfied.

7.   Products to be used in smoke and heat control systems

Table 7.1

Applies to

Single compartment smoke control ducts

E600

 

15

20

30

45

60

90

120

180

240

360

S

5  m3 /(m2 h) maximum leakage rate with reference to duct surface area at ambient temperature and 5  m3 /(m2 h) maximum leakage rate related to the duct surface area during the fire test.

Notes

In addition to meeting the requirements related to integrity (E) the duct must also achieve 10  m3 /(m2 h) maximum leakage rate with reference to duct surface area during the fire test.

The classification is completed by the suffix ‘single’ for products intended to be used for single compartment use only.

‘ve’ and/or ‘ho’ indicate that the product is intended to be used for vertical and/or horizontal use, within the compartment.

‘500 ’, ‘1 000 ’, ‘1 500 ’ indicate the product is intended to be used up to these values of under-pressure, measured in Pa at ambient temperature.


Table 7.2

Applies to

Multi-compartment fire resistant smoke control ducts

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

S

5  m3 /(m2 h) maximum leakage rate with reference to duct surface area at ambient temperature and 5  m3 /(m2 h) maximum leakage rate related to the duct surface area during the fire test.

Notes

In addition to meeting the requirements related to integrity (E) the duct must also achieve 10  m3 /(m2 h) maximum leakage rate with reference to duct surface area during the fire test.

The classification is completed by the suffix ‘multi’ for products intended to be used for multi-compartment use.

‘ve’ and/or ‘ho’ indicate that the product is intended to be used for vertical and/or horizontal use.

‘500 ’, ‘1 000 ’, ‘1 500 ’ indicate that the product is intended to be used up to these values of under-pressure, measured in Pa at ambient temperature.


Table 7.3

Applies to

Single compartment smoke control dampers

E600

 

15

20

30

45

60

90

120

180

240

360

S

200  m3 /(m2 h) maximum leakage rate with reference to nominal duct cross sectional area:

(a)

smallest size at ambient temperature;

(b)

largest size at ambient temperature and during the fire test.

Notes

In addition to meeting the requirements related to integrity (E) the single compartment smoke control damper must also:

(a)

be tested from both sides;

(b)

pass a maintenance of opening test; and

(c)

achieve 360  m3 /(m2 h) maximum leakage rate with reference to nominal duct cross sectional area during the fire test

(1)

smallest size at ambient temperature; and

(2)

largest size at ambient temperature and during the fire test.

The classification is completed by the suffix ‘single’ for products intended for single compartment use.

‘ved’, ‘vew’, ‘vedw’ and/or ‘hod’, ‘how’, ‘hodw’ indicate that the product is intended to be used for vertical and/or horizontal use, together with mounting in a duct or in a wall/floor or both respectively.

‘H’ indicates a single compartment smoke control damper capable of satisfying integrity (E) for the classification period having a horizontal blade axis or geometry,

‘V’ indicates a single compartment smoke control damper capable of satisfying integrity (E) for the classification period having a vertical blade axis or geometry.

‘500 ’, ‘1 000 ’ and ‘1 500 ’ indicate that the product is intended to be used up to this value of under-pressure in Pa at ambient temperature.

‘AA’ denotes for use with applications providing automatic activation, ‘MA’ denotes for use with applications requiring manual intervention or providing automatic activation.

‘C300 ’, ‘C10 000 ’, ‘CMOD’ or ‘C300 (N)’, ‘C10 000 (N)’, ‘CMOD(N)’ indicate the product is intended to be used in smoke control only systems, fully controlled smoke control systems and smoke control systems combined with environmental systems or modulating smoke control dampers intended to be used in any system having a controlled or variable position, tested under load, or without load (N), respectively.

‘HOT 400 /30 ’ (High Operational Temperature) indicates that the single compartment smoke control damper has been subjected to an additional test to demonstrate that it has the ability to be opened and closed during a period of 30 minutes of temperatures up to 400  °C.


Table 7.4

Applies to

Multi-compartment fire resistant smoke control dampers

E

 

15

20

30

45

60

90

120

180

240

360

EI

 

15

20

30

45

60

90

120

180

240

360

S

200  m3 /(m2 h) maximum leakage rate with reference to nominal duct cross sectional area:

(a)

smallest size at ambient temperature;

(b)

largest size at ambient temperature and during the fire test.

Notes

In addition to meeting the requirements related to integrity (E) or integrity and insulation (EI) the multi-compartment fire resistant smoke control damper must also:

(a)

be tested from both sides;

(b)

pass a maintenance of opening test; and

(c)

achieve 360  m3 /(m2 h) maximum leakage with reference to nominal duct cross sectional area during the fire test

(1)

smallest size at ambient temperature; and

(2)

largest size at ambient temperature and during the fire test.

The classification is completed by the suffix ‘multi’ for products intended for multi-compartment use.

‘ved’, ‘vew’, ‘vedw’ and/or ‘hod’, ‘how’, ‘hodw’ indicate that the product is intended to be used for vertical and/or horizontal use, together with mounting in a duct or in a wall/floor or both respectively.

‘H’ indicates a multi-compartment fire resistant smoke control damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a horizontal blade axis or geometry.

‘V’ indicates a multi-compartment fire resistant smoke control damper capable of satisfying integrity (E), or integrity and insulation (EI) for the classification period having a vertical blade axis or geometry.

‘500 ’, ‘1 000 ’ and ‘1 500 ’ indicate that the product is intended to be used up to this value of under-pressure in Pa at ambient temperature.

‘AA’ denotes for use with applications providing automatic activation, ‘MA’ denotes for use with applications requiring manual intervention or providing automatic activation.

‘C300 ’, ‘C10 000 ’, ‘CMOD’ or ‘C300 (N)’, ‘C10 000 (N)’, ‘CMOD(N)’ indicate that the product is intended to be used in smoke control only systems, fully controlled smoke control systems and smoke control systems combined with environmental systems or modulating smoke control dampers intended to be used in any system having a controlled or variable position, tested under load, or without load (N), respectively.

‘HOT 400 /30 ’ (High Operational Temperature) indicates that the multi-compartment fire resistant smoke control damper has been subjected to an additional test to demonstrate that it has the ability to be opened and closed during a period of 30 minutes of temperatures up to 400  °C.


Table 7.5

Applies to

Smoke barriers

D600

 

15

20

30

45

60

90

120

180

240

360

DH

 

15

20

30

45

60

90

120

180

240

360


Table 7.6

Applies to

Powered smoke and heat control ventilators (fans), including connectors

F200

 

15

20

30

45

60

90

120

180

240

360

F300

 

15

20

30

45

60

90

120

180

240

360

F400

 

15

20

30

45

60

90

120

180

240

360

F600

 

15

20

30

45

60

90

120

180

240

360

F842

 

15

20

30

45

60

90

120

180

240

360


Table 7.7

Applies to

Natural smoke and heat exhaust ventilators

B300

 

15

20

30

45

60

90

120

180

240

360

B600

 

15

20

30

45

60

90

120

180

240

360

Βθ

 

15

20

30

45

60

90

120

180

240

360

Notes

Where θ indicates the exposure condition (temperature), higher than 300 °C.

These products are designed to open in case of fire and do not have an integrity (E) classification.


ELI: http://data.europa.eu/eli/reg_del/2026/557/oj